This all on same breaker. Left, spliced wires are hot, but do nothing and there’s no switch for them.

Wires on the right are on a switch that controls two other lights closer to the breaker.

Can I just removed the splice and terminate the hot wires into a box mounted on the rafter?

i think the spliced goes to these wires, then leads somewhere else?

  • Treczoks@lemmy.world
    link
    fedilink
    arrow-up
    3
    ·
    11 hours ago

    I was tasked to install the lights in an annex to my sisters “new” place - an annex to a centuries old timberframe house, with a big mess of an installation. Fusebox was a total chaos, several generations of fuses, and nothing documented. So I removed the main fuse, went up the ladder and wanted to unscrew a terminal - and found myself down at the floor again. Took out measuring tools, found nothing.

    Went to the fusebox, checked every outgoing line, nothing. Went back into the annex, climbed up the ladder again, but measured before I started again. And found power! I simply shorted this (carefully!), it went “fump”, and power was gone again. But while I was standing on this ladder, measuring, the multimeter suddenly showed power again!

    In the end, I found out that the annex was not powered by the house, but by the neighbors house. And they obviously had put the fuse back in that I popped out for them…

  • ThisOne@lemmy.world
    link
    fedilink
    English
    arrow-up
    17
    ·
    edit-2
    1 day ago

    Wagos my man, wagos. Its wire nuts from the future.

    Kill the breaker undo whatever the monstrosity is. Each hot, neutral, and ground gets its own Wago. You buy the type that has enough holes for your problem. If theres 3 hot legs that all should all go together after you remove the fixtue get (3) 3-holes (one for 3 hots one for 3 neutrals one f0r 3 grounds). Strip the hot wires so theres no bare copper outside the Wago and clip em all in the Wago, do the neutrals and grounds in their own wagos and your done. No fire haze. Safer than wire nuts and easier. And I’m not a salesman just used em before.

    Wagos!

    probably you need 12awg size (the thickness of the copper cable)

    Hardware store or amazon. Seriously easy. Cheap. No need for a box. Works just as well for weird 4 wire 277v or whatever.

    …just dont put hot and neutral together. Hots with hots neutrals with neutrals…

    • JeanValjean@piefed.social
      link
      fedilink
      English
      arrow-up
      10
      ·
      1 day ago

      I agree with using the Wagos, as they are the best thing ever for tying wires together. Get a bunch of 2 and 3 holes, and a 25 pack of five holes. Grounds need to be continuous so they get pigtailed to the fixture under the green screw, and under the box screw if you use a metal box, which I generally use in ceilings. If your box is metal and doesn’t have a ground screw, they sell them at the hardware store as well.

      I would argue that a splice should always be in a box or within a rated fixture to keep home inspectors and code inspectors happy. Boxes must be accessible. Your local Authority Having Jurisdiction may allow them to be behind a drop ceiling, but you cannot drywall over them without cutting a hole and adding a blank plate.

      If you’re joining to existing, it looks like you’ll need 12 awg as mentioned above. If pulling all new you can use 14 awg since led fixtures are unlikely to ever pull 15 amps, though I rewired the outlets and fixtures in my garage with all 12 awg for future proofing and would recommend the same. You can put a 15A breaker on 12 awg but not a 20A on 14 awg.

      For wire made since around 2001, yellow is 12 awg and white is 14 awg. For wire before that, you need to read the jacket.

  • WhiteOakBayou@lemmy.world
    link
    fedilink
    arrow-up
    9
    ·
    1 day ago

    If there are two hot wires for that it seems most likely they went to a switch at some point. I doubt what you have now would burn down the house anytime soon but putting them in a box is a good idea. If it was me I’d get circuit tracer and verify your hunch about them going to that old wall box. If they ended up not going there I’d just do the splice properly, shove it in a box and never think about it again.

    • bluGill@fedia.io
      link
      fedilink
      arrow-up
      2
      ·
      1 day ago

      don’t label with panel slot - too often you need to move things and so those are incorrect anyway

      • JeanValjean@piefed.social
        link
        fedilink
        English
        arrow-up
        3
        ·
        1 day ago

        My preference is to always remove wires that aren’t powered to the greatest extent practicable. You don’t want someone in the future deciding they can just randomly use the wire and burn the house down.

  • jbellows@piefed.social
    link
    fedilink
    English
    arrow-up
    2
    ·
    22 hours ago

    This reminds me of a Talking Heads song. Very popular in the early 80s. Groovy intro, better than groovy chorus. Can’t remember the name for the life of me…

  • bluGill@fedia.io
    link
    fedilink
    arrow-up
    2
    ·
    1 day ago

    the box needs to be accessable. The drop ceilling counts but something perminant ceiling would not.